HVAC NOW
March 8, 1996
Dehumidification Pays Dividends
Liquid Pressure Amplifiers' Hy-Dry Coil Significantly Reduces
Building Humidity Levels
By John Bergfeld
The patented Hy-Dry (TM) System
One function of an Air Conditioning system is to remove moisture from the air. In many
areas, it may be the most important function of the system. This moisture removal can
consume more power than cooling the air. It is for this reason that Hy-Save Inc. studied
different methods of humidity control and developed the Hy-Dry(TM) System. This
technology will not only out perform other methods, but will do it in a cost effective
manner and generate a very good return on investment.
Theory of the Hy-Dry (TM) System
In an air conditioning system it is the evaporator that removes the moisture. It would
therefore seem reasonable that increasing the efficiency of the evaporator would increase
the ability to remove moisture. On many systems, a second step in dehumidification is to
reheat the air in order to further lower the relative humidity after removing the
moisture. If both of these functions can be accomplished at the same time, the desired
operation is greatly enhanced.
Hy-Save Inc. addressed these two components of the dehumidification process by
utilizing the LPA (Liquid Pressure Amplification) Technology to pump the liquid
refrigerant through a subcool/reheat coil placed downstream from the evaporator (Figure
2). In this manner, liquid refrigerant is deeply subcooled on it's way to the expansion
valve (TXV), resulting in a dramatic improvement in evaporator performance and moisture
removal. At the same time, the heat removed from the liquid refrigerant is used to reheat
the supply air stream which reduces the relative humidity of the air delivered. Low dew
point subcooling/reheat coils have in fact been used for years, but only through the use
of the LPA technology to overcome the pressure losses through the liquid line and
subcool/reheat coil can this be accomplished without a significant loss in capacity.

Figure 1
First let us look at a pressure enthalpy chart (Figure 1) to see what is happening. For
this analysis, we will use the standard 105 degree condensing temperature with the same
liquid temperature. Depending on the size of the Hy- Dry (TM) coil, liquid
should be able to be sub cooled to within 5 to 8 degree F of the air temperature leaving
the evaporator. As a rule, this will gain 0.5% capacity increase for each degree of
subcooling, and that capacity increase is clearly outlined on the pressure enthalpy chart.
As an example, with 60 degree F leaving air, we should be able to subcool the liquid to 68
degree F. With 105 degree F normal liquid temperature, this would be 37 degree F of
subcooling, or a capacity increase of 18.5% (this capacity increases is a direct result of
the cooler refrigerant).

Figure 2
As the liquid exits the TXV, a certain portion will boil off just to cool the
refrigerant to the saturation temperature. This flash off of liquid only cools the
refrigerant and does not remove heat in the evaporator. However, the compressor sees it as
additional work and must still compress this vapor. The colder the entering refrigerant,
the less excess vapor there is to be recompressed. In addition, as can be seen on a
pressure enthalpy chart, the percent quality of the refrigerant improves from about 72%
liquid without subcooling to about 83% liquid with the Hy-Dry (TM) coil in
operation. So that is how subcooling helps remove more moisture from the air and the next
step is reheat.
Computer rooms and other applications that require strict relative humidity control
have long used reheat. Essentially, the air is over cooled to remove moisture and then
reheated to raise the temperature back to the set point. This process of reheating also
provides a lower relative humidity air. This technique is energy intensive since added
cooling is required and energy to reheat the air is required, one might say a lose-lose
energy situation. With Hy-Dry (TM) it is a win-win energy situation. The heat
is removed from the refrigerant (subcooling = win). and is used for "free"
reheating (lower relative humidity = win). No extra or external energy is used. So from
all the above it should be clear why Hy-Dry (TM) combines win-win factors to
improve overall system efficiency.
THE HY-DRY (TM) SYSTEM PUT TO THE TEST
Theory and calculations are fine but do they really work? Hy-Save Inc. built a working
model to test the Hy-Dry (TM) theory. The unit was monitored every 60 seconds
using a data logger. Most of the calculations proved to be quite accurate, however the
moisture removal capabilities had been greatly underestimated. The test found that at 65%
relative room humidity 50% more water was removed with the Hy-Dry (TM) system
than without the Hy-Dry (TM) coil. In order to further check for moisture
removal, the condensate water leaving the coil was captured and weighed, verifying the
data logger results. At the same time, reductions in head pressure and suction pressure
were also observed. The icing on the cake was that this increase in performance was
achieved with a reduction in energy consumption of about 12%.
THE HY-DRY (TM) SYSTEM PUT TO WORK IN THE ETL TESTING LABORATORIES
In order to provide certified ratings, a manufacturer must have the performance of the
equipment evaluated at a National Testing Laboratory. These test are done under ARI
standards of 80 degrees F Dry Bulb and 67 degrees F Wet Bulb temperatures of the entering
air. The laboratory results for one manufacturer's equipment showed at 50% relative
humidity entering air, 44% more moisture is removed with the Hy-Dry (TM)
system.
The manufacturer of this line of AC equipment conducted test of Hy-Dry (TM)
at their facilities prior to sending it out for certification. These test were conducted
with 35% relative humidity entering the evaporator. Under these conditions over 200% more
moisture was removed when compared to the same system without the Hy-Dry (TM)
system operating.
THE HY-DRY (TM) SYSTEM PUT TO WORK IN THE FIELD
The Hy-Dry(TM) system moved from the working model into the field with several
applications installed in the State of Florida. The results were again better than
predicted with dramatic reductions in relative humidity accompanied by reductions in
energy consumption.
At the Florida Department of Health and Rehabilitative Services (HRS) Crystal lake
Service Center in Pompano Beach, Florida; six brand new Trane 30 Ton and one 40 Ton split
package units were retrofitted with the Hy-Save LPA(TM), Liquid Injection, and
Hy-Dry (TM) Technology. During ambient conditions of 89 degrees F dry Bulb and
83% RH, the monitoring showed a 32% reduction in relative humidity inside the building
from 66% to 45% relative humidity (RH).
An installation at the North Marion High School in Sparr Florida, showed a 67% increase
in total cooling BTU's, a 49.7% decrease in KW per Ton, and a 20% overall reduction in RH,
all of which was accomplished under ambient conditions that went from 35% RH during the
monitoring before retrofit to 90% RH after installation. Monitoring by the local Utility,
Florida Power Corp. showed a decrease in KW demand of 22%.
BENEFITS OF THE HY-DRY (TM) SYSTEM INDOOR AIR QUALITY
High relative humidity is a major contributor to what has come to be know as the
"sick building syndrome". The Hy-Dry (TM) system will lower relative
humidity in the cooling duct delivery system helping to prevent the growth of mold,
bacteria and other biological contaminants.
ENERGY SAVINGS
When the relative humidity is lowered with the Hy-Dry (TM) system the
thermostat can be raised while maintaining occupant comfort levels. This reduction in load
on the compressor can translate into 2.5% savings or more for each degree thermostats are
raised. In supermarket applications, reduced humidity levels will reduce the refrigeration
loads, reduce the number of defrost cycles necessary, and reduce the need for anti-sweat
heaters.
ECONOMICAL INSTALLATION
The installation of the Hy-Save LPA (TM) and Hy-Dry (TM)
technologies is far less than competing technologies. Heat pipe installation is around
twice the cost and a typical Desiccant Wheel system is four times the cost. The Desiccant
Wheel also requires higher energy costs after installation to remove the moisture.
Installation of the Hy-Dry (TM) system is relatively simple, requiring only one
extra coil, an LPA (TM), and some piping. Disruptions to existing operations is
minimal.
PERFORMANCE
The Hy-Dry (TM) system increases capacity by as much as 20% and requires no
additional fan horsepower. Heat Pipe technology will reduce capacity and may require the
use of additional fan HP. Some form of heat is required to dry out the desiccant wheel and
this is added energy that is above refrigeration energy use.
COMFORT FOR BUILDING OCCUPANTS
Humidity is a major factor in determining the comfort zone for occupants. Reducing the
relative humidity through the use of the (TM) system will increase the level of
comfort.
ECONOMICAL OPERATION
The LPA (TM) floating head, Liquid Injection and Hy-Dry (TM) systems
will allow cooling equipment to operate at maximum efficiency throughout the year, costing
less to do a better job. The Hy-Dry (TM) system does not have the high
maintenance and operational cost associated with some competitive technologies and will in
fact extend the life of compressors by allowing them to operate at reduced head pressures
and temperatures.
By-Line: John Bergfeld is on the Board of Directors of APEC (Association
of Professional Energy Consultant) which has a goal of "Bridging the Technology
Gap" by providing technology transfers of information.
THE HY-DRY (TM) SYSTEM IS THE SUPERIOR
SOLUTION TO INDOOR AIR QUALITY AND EFFICIENCY IN AIR CONDITIONING/REFRIGERATION
APPLICATIONS !
|